How to Configure Instruction Control for Alarm Monitoring System Application at xPortalNet HS Client

How to Configure Instruction Control for Alarm Monitoring System Application at xPortalNet HS Client

Problem (Issue) Statement:

How to configure Instruction Control for alarm monitoring system application at xPortalNet HS Client

Description:

A guide to configure Instruction Control for alarm monitoring system application at xPortalNet HS Client

Related Software:

  • xPortalNet HS v1.5.0.22

Related Hardware:

  • XP-GLS5000 v1.16
  • XP- SNET- E32R
  • XP-SNET- E248

System Application:

Alarm Monitoring System

Symptom and Finding:

NA

Cause:

For first time configuration on Instruction Control for alarm monitoring system application at xPortalNet HS Client

Solution:

Warning!

  • Users are not recommended to run any xPortal software in Windows XP operating system as the system is unstable

  • Users are also advised to stop the xPortal Services before shutting down the Server PC to prevent any missing transaction issues.

.

.

Summary:



Step-by-step Guide:

  • Ensure that the xPortalNet HS Services is Running:

Step 1: Open xPortalNet Comm Service.


Step 2: Ensure that the xPortalNet Comm Service Status is Running.
xPortalNet Comm Service Running Pop-up Message
Figure 1: xPortalNet Comm Service Running Pop-up Message
.

.

  • Ensure that the alarm monitoring controller settings are configured in xPortalNet Server:

Knowledge Base Link

.

.

  • To configure Instruction Control setup at xPortalNet HS client:

Step 1: Go to xPortalNet HS ClientSystem Setting Instruction Control. The Instruction Setup window will be shown as below:
Instruction Setup Window
Figure 2: Instruction Setup Window


Step 2: Click Add to create a new instruction. The Add Instruction window will be shown as below. Fill in the respective fields and click OK to save changes.
Add Instruction Window
Figure 3: Add Instruction Window


.

Note

  • *represents required field
  • Users can add up to a maximum of 8 Inputs and Outputs in one Instruction Setup.

.

.

Step 3: Repeat steps 1 and 2 to add additional Instruction Setups as necessary.


Step 4: The following message window will be shown Record Added and click OKbutton.
Record Added Window
Figure 4: Record Added Window
.

.

  • To send Door Setting to Controller after complete the configuration:

Step 1: After completing the configuration settings, users MUST send all settings to the controller.


Step 2: Go to Device Comm>Send Door Setting.
Send Door Setting Button
Figure 5: Send Door Setting Button


Step 3: Select the controller to send all settings. Click Send All Settings to send all configuration settings to the selected controller.


Step 4: The Delivery Report will be prompted. Ensure that software have sent all configuration settings successfully.
.

.

  • To observe the device status:

Step 1: To check the status of the controller, go to xPortalNet HSClient>Device List>Controller List to verify that the controller Status is Up.
Controller List Under Device List Tab
Figure 6: Controller List under Device List tab

Step 2:To check the status of the controller, go to xPortalNet HSClient>Device List>Alarm Controller Listto verify that the alarm controller Status is Up.
Alarm Controller List under Device List Tab
Figure 7: Alarm Controller List under Device List tab


Step 3: To check the status of the controller, go to xPortalNet HS Client>Output List to verify that the output Status is OFF.
Output List Under Device List Tab
Figure 8: Output List under Device List tab




Common Issue:

NA

Date Documentation:

28/5/2019 (Rev 1.1)

PROOF-READ

.

Related Articles.

Containing the label "xp-gls5000"

Filter by label

There are no items with the selected labels at this time.

.


.

Related content

How to Configure Instruction Control for Alarm Monitoring System Application at xPortalNet Client
How to Configure Instruction Control for Alarm Monitoring System Application at xPortalNet Client
More like this
How to Setup Alarm Monitoring System Application Using XP-GLS5000 Controller at xPortalNet HS Server
How to Setup Alarm Monitoring System Application Using XP-GLS5000 Controller at xPortalNet HS Server
More like this
How to Configure Alarm Configuration in xPortalNet Software
How to Configure Alarm Configuration in xPortalNet Software
More like this
How to Assign XP-GLS5000 Controller to Function as Alarm Monitoring Controller in xPortalNet HS Server Software
How to Assign XP-GLS5000 Controller to Function as Alarm Monitoring Controller in xPortalNet HS Server Software
More like this