How to Set Output Time Zone for XP-SNET Controller in xPortalNet Software

Problem (Issue) Statement:

How to set Output Time Zone for XP-SNET controller in xPortalNet software

Description:

This article will guide users to set Output Time Zone for XP-SNET controller in xPortalNet software.

Related Software:
  • xPortalNet
Related Hardware:NIL
System Application:NIL
Symptom and Finding:NIL
Cause:For first time guide to set Output Time Zone for XP-SNET controller in xPortalNet software.
Solution:

Summary:

  • To set Output Time Zone for XP-SNET controller in xPortalNet software.

.

.

Step-by-step Guide:
  • To set Output Time Zone for XP-SNET controller in xPortalNet software:

Step 1: At the XP-SNET controller, set the DIP switch 2 and 3 of the SETTING DIP switch to the ON position.
SETTING DIP Switch on XP-SNET Controller
Figure 1: SETTING DIP Switch on XP-SNET Controller

.

Step 2: Reset the controller after the DIP switches are adjusted.
RESET Button on XP-SNET Controller
Figure 2: RESET Button on XP-SNET Controller

.

Step 3: Go to xPortalNet Server > Server Admin > System Device Setup > Alarm Controller > Add. The Add Alarm Controller window will be shown. Set the Unit No. as "10", and select the Model No as "Built-In IO".
Add Alarm Controller Window
Figure 3: Add Alarm Controller Window

.

Step 4: Next, go to xPortalNet Server > Server Admin > System Device Setup > Output Point > Add. The Add Output window will then be shown.
Add Output Window 
Figure 4: Add Output Window 

.

XP-SNET controller has 3 extra outputs (relay no 6, 7, and 8) to be used for alarm monitoring. Refer to the table below for the respective Point No to set in the software.

.

.

Step 5: Go to xPortalNet Client > Data Setup > System Setting > Outputselect the correct Output > Modify. The Edit Output window will then be shown. Under the Output TZ field, select the pre-configured Time Zone.
Edit Output Window
Figure 5: Edit Output Window

.

Knowledge Base Link

Users may refer to How to Configure Time Zone Settings in xPortalNet Software for the complete steps on how to configure Time Zone settings in xPortalNet software.

Common Issues:

NIL

Porting Date:22/01/2020

PROOF-READ

.

Related Articles.

Containing the label "xportalnet"

Filter by label

There are no items with the selected labels at this time.

.


.

© MicroEngine Technology Sdn Bhd (535550-U). All rights reserved.