How to Troubleshoot the Issue where the XP-M1000i or XP-M1300i Controller is Down

Problem (Issue) Statement:How to troubleshoot the issue where the XP-M1000i controller is down
Description:

This article will guide users on how to troubleshoot the issue where the XP-M1000i or XP-M1300i controller is down

Related Software:
  • xPortalNet
  • xPortal3000
Related Hardware:
  • XP-M1000i
  • XP-M1300i
System Application:NIL
Symptom and Finding:
  • controller status is shown as down
  • no communication from controller to the software (no transaction is shown in the software)
Cause:
  • Test Mode (JP6) jumper at XP-M1000i or XP-M1300i controller is shorted
  • Controller not properly connected to Server PC
  • Incorrect software setting

Warning!

We do not recommend controllers and PC communication to be connected via Wifi (using Wifi dongles) as Wifi connection is unstable and can make controller statuses be shown as "Down".

.

.

  • To ensure that Test Mode (JP6) jumper is opened:

Step 1: At the controller board, locate the Test Mode (JP6) jumper. Ensure that the jumper is opened.
Test Mode Jumper on XP-M1000i or XP-M1300i Controller
Figure 1: Test Mode Jumper on XP-M1000i or XP-M1300i Controller

.

.

  • To check the Uplink connection:

LAN Connection:

Step 1: Please ensure that the LAN cable is functional (check using cable tester) and ensure that the LAN cable is properly plugged into the LAN cable port on the controller. Ensure that the Yellow LED on the port is blinking, indicating that communication is established.

.

.

RS485 Connection:

Step 1: Please ensure that the connection to MCI is properly connected as shown by the following wiring diagram
Connection to MCI
Figure 2: Connection to MCI

.

Step 2: For RS485 connection, users have to set the baud rate jumper according to the following diagram. Ensure that the baud rate setting here is the same as the baud rate setting in the software.
Baud Rate Jumper Settings
Figure 3: Baud Rate Jumper Settings

.

.

  • To check the software setting:

LAN Connection:

Step 1: Please configure the network settings on the software correctly. Ensure that users assign a unique IP Address to the controller.

Knowledge Base Link

Users may refer to How to Pre-configure Network Connection for IP Controllers for the complete guide on how to configure the network settings

.

.

RS485 Connection:

Step 1: Please configure the software settings correctly. Ensure that the Baud Rate configured in the software is the same as the baud rate jumper settings on the controller.

Knowledge Base Link

Users may refer to How to Configure XP-M1000i or XP-M1300i Controller Using RS485 or RS232 Connection for the complete guide on how to configure the controller for RS485 connection.

Common Issues:NIL
Porting Date:16/4/2019

PROOF-READ

.