Why the XP-SNET-E32R extension board is unable to show UP status after sending door setting to XP-SNET controller for Lift Masking Application
Problem (Issue) Statement: | Why the XP-SNET-E32R extension board is unable to show UP status after sending door setting to XP-SNET controller for Lift Masking Application |
Description: | Why the XP-SNET-E32R extension board is unable to show UP status after completing software configuration and sending all door settings to XP-SNET controller? |
Related Software: |
|
Related Hardware: |
|
System Application: |
|
Symptom and Finding: | After checking software configuration and re-sending all door settings to XP-SNET controllers again, xPortalNet Client > Device List > Alarm Controller List still showed XP-SNET-E32R extension board for Blk A Lift 1 is "Down" status. |
Cause: | After logging in to Web Diagnostic of XP-SNET to check the System Information, it is discovered that DIPs Setting value is set as "00". (XP-SNET controller is configured as Door Controller) |
Solution: | Warning! The XP-SNET controller will not send fire alarm signal over to the connected XP-SNET-E32R and/or XP-SNET-E248 extension boards if the configuration settings for the XP-SNET controller is not completed.Complete the configuration settings for XP-SNET controller in order for XP-SNET-E32R and/or XP-SNET-E248 to respond accordingly to fire alarm signals.. . Summary:
Step-by-step Guide:
Step 1: Go to Lift Motor Room and open the XP-SNET enclosure cover.
If the LED D77 is turned off after setting the DIP switch 1 under SETTING, and the DIPs Setting of Web Diagnostic is still indicating the value of "00", the XP-SNET controller board might be faulty. |
Date Documentation: | 26/7/2018 (Rev 1.0) |