How to Setup Alarm Monitoring System Application Using XP-SNET Controller at xPortalNet Server

Problem (Issue) Statement:

How to setup alarm monitoring system application using XP-SNET controller at xPortalNet Server

Description:

A guide to configure alarm monitoring system application using XP-SNET controller at xPortalNet Server.

Related Software:

  • xPortalNet v1.5.0.122

Related Hardware:

  • XP-SNETv2 v3.48
  • XP-SNET-E32R
  • XP-SNET-E248

System Application:

  • Alarm Monitoring System

Symptom and Finding:

NA

Cause:

For first time configuration for alarm monitoring system application using XP-SNET controller at xPortalNet Server.

Solution:

Warning!

The XP-SNET controller will not send fire alarm signal over to the connected XP-SNET-E32R and/or XP-SNET-E248 extension boards if the configuration settings for the XP-SNET controller is not completed.

Complete the configuration settings for XP-SNET controller in order for XP-SNET-E32R and/or XP-SNET-E248 to respond accordingly to fire alarm signals.

.

.

Summary


Step by Step Guide:

  • To configure XP-SNET Controller to function as Alarm Monitoring controller:

Step1: Turn "ON" DIP switch 3 under SETTING on XP-SNET controller for Alarm Monitoring Mode. Ensure that all other DIP switches remained as "OFF".
The DIP Switches for Controller SETTING on the XP-SNET Controller
Figure 1: The DIP switches for controller SETTING on the XP-SNET controller


Step 2: The following table explains the functions of the DIP switches for controller SETTING on the XP-SNET controller:



Step 3: After configuring the DIP switches, press "RESET" on the XP-SNET controller to reset the controller in order for the new settings to take effect.


  • Ensure that xPortalNet Services is Running:

Step 1: Open xPortalNet Comm Service.


Step 2: Ensure that the xPortalNet Comm Service Status is Running.
xPortalNet Comm Service Running Pop-up Message
Figure 2: xPortalNet Comm Service Running pop-up message


  • To configure Connection Setup:

Step 1: Login to xPortalNet Server.


Step 2: Go to Server Admin > Connection Setup. The Connection Setup window will be shown as below:
Connection Setup Window
Figure 3: Connection Setup window


Step 3: Click Add to add a new connection. The Add Connection window will be shown as below. Fill in the respective fields and click OK to save changes.
Add Connection Window
Figure 4: Add Connection window




  • To configure Controller Setup:

Step 1: Go to xPortalNet Server > Server Admin > System Device Setup > Controller. The Connection Setup window will be shown as below:
Controller Setup Window
Figure 5: Controller Setup window


Step 2: Click Add to add a new controller device. The Add Connection window will be shown as below. Fill in the respective fields and click OK to save changes.
Add Controller Window
Figure 6: Add Controller window




Step 3: The following message window will be prompted to show that Record is Added. Click OK to continue.
Record Added Window
Figure 7: Record Added window



  • To configure Alarm Controller Setup:

Step 1: Go to xPortalNet Server > Server AdminSystem Device SetupAlarm Controller. The Alarm Controller Setup window will be shown as below:
Alarm Controller Setup Window
Figure 8: Alarm Controller Setup window


Step 2: Click Add to add a new alarm controller device. The Add Alarm Controller window will be shown as below. Fill in the respective fields and click OK to save changes.
Add Alarm Controller Window
Figure 9: Add Alarm Controller window



Note

For internal I/O configuration on XP-SNET controller, the Unit No field MUST be configured to "10"



Step 3: The following message window will be prompted to show that Record is Added. Click OK to continue.
Record Added Window
Figure 10: Record Added window
.

Note

Repeat steps 1 to 3 under this section for all extension boards (XP-SNET-E32R and XP-SNET-E248S) connected to the XP-GLS5000 controller board for alarm monitoring purposes.

For applications where more than one extension board is connected to the XP-GLS5000 controller board, configure the address of the alarm panel in increasing order. For example,
 - 1st extension board address = "00", 
 - 2nd extension board address = "01", 
 - 3rd extension board address = "02" , 
and so on.

In the Add Alarm Controller window, configure the Unit No. field according to the extension board address configured.

.

.

  • To configure Output Setup:

Step 1: Go to xPortalNet Server > Server AdminSystem Device Setup > Output Point. The Output Setup window will be shown as below:
Output Setup Window
Figure 11: Output Setup window


Step 2: Click Add to add a new output device. The Add Output window will be shown as below. Fill in the respective fields and click OK to save changes.
Add Output Window
Figure 12: Add Output window



Note

The output point number starts from "0" for both extension boards XP-SNET-E32R and XP-SNET-E248.




Step 3: The following message window will be prompted to show that Record is Added. Click OK to continue.
Record Added Window
Figure 13: Record Added window



  • To configure Input Setup:

Step 1: Go to xPortalNet Server > Server AdminSystem Device Setup > Input Point. The Input Setup window will be shown as below:
Input Setup Window
Figure 14: Input Setup window


Step 2: Click Add to add a new input device. The Add Input window will be shown as below. Fill in the respective fields and click OK to save changes.
Add Input Window
Figure 15: Add Input window




Note

The input point number starts from "0" for the XP-SNET-E248 extension board.




Step 3: The following message window will be prompted to show that Record is Added. Click OK to continue.
Record Added Window
Figure 16: Record Added window


Step 5: Users can then proceed to create an Instruction Control to configure the relationship between the Inputs and Outputs.


Knowledge Base Link

Date Documentation:

23/5/2018 (Rev 1.0)

PROOF-READ

.

.


.

© MicroEngine Technology Sdn Bhd (535550-U). All rights reserved.