Problem (Issue) Statement: | How to configure XP-SNET for door access | |||||||||||||||||||||||||||||||||||||||||||
Description: | This article will guide users on how to configure XP-SNET for door access. | |||||||||||||||||||||||||||||||||||||||||||
Related Software: | NIL | |||||||||||||||||||||||||||||||||||||||||||
Related Hardware: |
| |||||||||||||||||||||||||||||||||||||||||||
System Application: | Door Access Mode | |||||||||||||||||||||||||||||||||||||||||||
Symptom and Finding: | NIL | |||||||||||||||||||||||||||||||||||||||||||
Cause: | For first time guide on how to configure XP-SNET for door access. | |||||||||||||||||||||||||||||||||||||||||||
Summary:
. Step-by-step Guide:
Step 1: Please ensure that the wiring termination for the XP-SNET controller is properly connected.
. . Step 2: At the SETTING DIP switch on the XP-SNET controller, turn ON DIP switch 2 and 3 for Door Access Mode and Alarm Monitoring Mode. . Step 3: Press the RESET button on the XP-SNET controller to reset the controller and allow the changes to take effect. . Step 4: Users can connect the relevant inputs and outputs to the XP-SNET controller accordingly. .
.
. .
. . Step 1: Go to xPortalNet Server > Server Admin > Connection Setup > Add. The Add Connection window will be shown. Fill up the information accordingly and click OK to continue. . Step 2: Go to xPortalNet Server > Server Admin > System Device Setup > Controller > Add. The Add Controller window will be shown. Fill up the information accordingly, and set the Unit No according to the controller ADDRESS DIP switch setting. Click OK to continue. . Step 3: Go to xPortalNet Server > Server Admin > System Device Setup > Door > Add. The Add Door window will then be shown. Fill up the information accordingly and click OK to continue. .
.
. .
Step 1: Users are required to send door settings to the newly configured controller.
| ||||||||||||||||||||||||||||||||||||||||||||
Common Issues: | NIL | |||||||||||||||||||||||||||||||||||||||||||
Porting Date: | 23/4/2019 |
...