How to Connect Multiple XP-M1000i or XP-M1300i Controllers to Server PC via RS485 Network

Problem (Issue) Statement:

How to connect multiple XP-M1000i / XP-M1300i controllers to Server PC via RS485 network

Description:

A guide to connect multiple XP-M1000i / XP-M1300i controllers to Server PC via RS485 network.

Related Software:

NA

Related Hardware:

  • XP-M1000i
  • XP-M1300i

System Application:

  • Door Access System
  • Vehicle Access System

Symptom and Finding:

NA

Cause:

For first time connection on multiple XP-M1000i / XP-M1300i controllers to Server PC via RS485 network.

Solution:

Note

  • For RS485 wiring connections between the controllers and the Server PC, the Daisy Chain connection topology is the recommended wiring connection.
  • The address of the controller must be unique (ranging from '00' to '15'), I.e. no two controllers in the same RS485 connection network can have the same address.
  • Each RS485 network bus can support up to a maximum of 16 controllers.

.

.

Knowledge Base Link

Users can refer to How to Configure RS485 Address for XP-M1000i or XP-M1300i Controller for instructions to configure the RS485 address for XP-M1000i/ XP-M1300i controller.

.

.

Warning!

RS485 wiring connection using the Star topology may result in controller communication issues!

.

.

Summary

  • Please follow wiring diagram as below:

Step 1: Wiring diagram for multiple XP-M1000i / XP-M1300i controllers to the Server PC via RS485 network:

Figure 1: Connection of multiple XP-M1000i / XP-M1300i controllers to the Server PC

Date Documentation:

19/6/2018 (Rev 1.1)