Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.
Comment: Added link to KB articles

...

Problem (Issue) Statement:

How to configure XP-SNET controller to integrate with turnstile system

Description:

A guide to configure XP-SNET controller to integrate with turnstile system.

Related Software:

  • xPortalNet Standard v1.5.0.154

Related Hardware:

  • XP-SNET v3.65
  • XP-MK800E v1.48
  • RDMFXE v3.01

System Application:

  • Turnstile Access System

Symptom and Finding:

NIL

Cause:

For first time configuration between XP-SNET controller and turnstile system for turnstile application integration.

Solution:

Summary:

Step-by-step Guide:

  • Anchor
    coldstart
    coldstart
    To perform ColdStart after first power up:
     

Step 1: Press & hold the COLDSTART button on XP-SNET controller board.

Step 2: Press & release RESET button on XP-SNET controller board.

Step 3: Wait for both STAT and CPU LED to light up at the same time.

Step 4: Release COLDSTART button.

Info
titleNote

Users are always recommended to perform ColdStart for new installations.




  • Anchor
    pre-config
    pre-config
    To perform pre-configuration setting on the network connection.


Info
titleKnowledge Base Link

Users may refer to /wiki/spaces/MICS/pages/128843793 to How to Pre-configure Network Connection for IP Controllers to complete the pre-configuration process.




  • Anchor
    ipconfig
    ipconfig
    To configure the IP address via Web Diagnostic.


Info
titleKnowledge Base Link

Users may refer to /wiki/spaces/MICS/pages/129073156 to How to Configure IP Address for IP Controllers to complete the configuration process.




  • Anchor
    enableexit
    enableexit
    To enable check exit
    reader door accessibility via Web Diagnostic:

Step 1: Open IE browser (Internet Explorer) and type the XP-SNET's IP address in the address box.


Info
titleNote

The default IP address for XP-SNET controller is 192.168.1.210




Step 2: Enter the Username and Password and click OK to continue. The Web Diagnostic window will be shown as below. Click Configuration to continue.
Configuration Tab in Web Diagnostic Home Page
Figure 1: Configuration Tab in Web Diagnostic Home Page


Step 3: Scroll down to Door Controller Setup section. Tick the Check exit reader door accessibility checkbox and click Confirm Change Door Setting to continue. Check Exit Reader Door Accessibility Checkbox
Figure 2: Check Exit Reader Door Accessibility Checkbox


Step 4: Click Log Out to exit from the web diagnostic.
Exiting from Web Diagnostic by Logging Out
Figure 3: Exiting from Web Diagnostic by Logging Out


  • Anchor
    mainconfig
    mainconfig
    To Configure Connection, Controller, and Door Setting for XP-SNET controller with xPortalNet


Info
titleKnowledge Base Link

User may refer to /wiki/spaces/MICS/pages/139853857 to How to Configure Connection, Controller, and Door Settings for XP-SNET controller with xPortalNet Software to complete the configuration process.




  • Anchor
    dooraccesslevel
    dooraccesslevel
    To configure Door Access Level for Visitor user


Info
titleKnowledge Base Link

User may refer to /wiki/spaces/MICS/pages/188711025 to How to Configure Door Access Level at xPortalNet Software to complete the configuration process.


Date Documentation:

24/7/2018 (Rev 1.0)

...