Problem (Issue) Statement:

How to terminate sensor wiring connection to extra inputs on XP-GLS5000 controller and to configure the inputs for alarm monitoring purposes.

Description:

A guide to terminate sensor wiring connection to extra inputs on XP-GLS5000 controller and to configure the inputs for alarm monitoring purposes.

Related Software:

  • xPortalNet HS v1.5.0.21 and above

Related Hardware:

  • XP-GLS5000

System Application:

  • Door Access System
  • Alarm Monitoring System

Symptom and Finding:

NA

Cause:

For first time connection and terminate wiring connection for extra inputs on XP-GLS5000 board.

Solution:

Summary:


Info
titleNote

XP-GLS5000 controller can be configured to operate in two different modes which allow users to configure the additional input for alarm monitoring purposes:

  • Door access with alarm monitoring
  • Alarm only mode

Different operation modes can affect the alarm input points available for configuration and termination.

.

.

Step-by-step Guide:

  • Anchor
    termination
    termination
    Wiring termination for inputs:

Step 1: Please refer to the wiring diagram below for alarm sensor input termination in door access with alarm monitoring mode. Users can use input terminal IN11 to IN16. Input terminal IN1 to IN10 are assigned for Door Access.
 
Figure 1: Wiring Termination Diagram for Input in Door Access with Alarm Monitoring Mode


Step 2: Please refer to the wiring diagram below for alarm sensor input termination in alarm mode only. Users can use all Input terminals from IN1 to IN16.
 
Figure 2: Wiring Termination Diagram for Input in Alarm Mode Only 


Info
titleNote
  • For alarm monitoring, the built-in input points on XP-GLS5000 controller only supports normally closed (NC) type sensor input termination.
  • For alarm monitoring applications using XP-SNET-E248 extension board, the extension board can support both normally closed (NC) and normally opened (NO) type sensor input termination.

.

.

  • Anchor
    configurecontroller
    configurecontroller
    To configure Alarm Controller Setup in xPortalNet Server:

Step 1: Go to Server Admin System Device Setup Alarm Controller Add. The Add Alarm Controller window will be shown as below:
Add Alarm Controller Window
Figure 3: Add Alarm Controller Window




Info
titleNote

For internal I/O configuration on XP-GLS5000 controller, the Unit No field MUST be configured to "10".

.

.

Step 2: The following message window will be prompted to show that the Record is Added. Click OK to continue.
 
Figure 4: Record Added Window
.

.

  • Anchor
    configureinput
    configureinput
    To configure Input Point Setup in xPortalNet Server:

Step 1: Go to Server Admin System Device Setup Input Point. The Input Setup window will be shown as below.
Input Setup Window
Figure 5: Input Setup Window


Step 2: Click Add to add a new input setup. The Add Input window will be shown as below. Fill in the respective fields and click OK to save the changes.
Add Input Window
Figure 6: Add Input Window



Step 3: The following message window will be prompted to show that Record is Added. Click OK to continue.
 
Figure 7: Record Added Window

.

Step 4: Users can proceed to configure built- in controller of Output Point and create an Instruction Controller to configure the relationship between the Inputs & Outputs points.
Info
titleKnowledge Base Link


Date Documentation:

15/8/2018 (Rev 1.0)

...

Section
bordertrue


Column
width100%

Related Articles.

Containing the label "xp-gls5000"

Filter by label (Content by label)
showLabelsfalse
max6
showSpacefalse
sorttitle
cqllabel = "xp-gls5000" and space = "MKB" and title ~ "!\"how to terminate sensor wiring connection to extra inputs on xp-gls5000 controller and to configure the inputs for alarm monitoring purposes\""


.

...

.

Choices for confluence
_id5d0b37eb1b57ee00208d4f66