Problem (Issue) Statement: | How to terminate sensor wiring connection to extra inputs on XP-GLS5000 controller and to configure the inputs for alarm monitoring purposes. | ||||||||||||||||||||||||||||||||||||||
Description: | A guide to terminate sensor wiring connection to extra inputs on XP-GLS5000 controller and to configure the inputs for alarm monitoring purposes. | ||||||||||||||||||||||||||||||||||||||
Related Software: |
| ||||||||||||||||||||||||||||||||||||||
Related Hardware: |
| ||||||||||||||||||||||||||||||||||||||
System Application: |
| ||||||||||||||||||||||||||||||||||||||
Symptom and Finding: | NA | ||||||||||||||||||||||||||||||||||||||
Cause: | For first time connection and terminate wiring connection for extra inputs on XP-GLS5000 board. | ||||||||||||||||||||||||||||||||||||||
Solution: | Summary:
..
Step 1: Please refer to the wiring diagram below for alarm sensor input termination in door access with alarm monitoring mode. Users can use input terminal IN11 to IN16. Input terminal IN1 to IN10 are assigned for Door Access.
. .
Step 1: Go to Server Admin > System Device Setup > Alarm Controller > Add. The Add Alarm Controller window will be shown as below:
. . .
Step 1: Go to Server Admin > System Device Setup > Input Point. The Input Setup window will be shown as below.
. Step 4: Users can proceed to configure built- in controller of Output Point and create an Instruction Controller to configure the relationship between the Inputs & Outputs points.
| ||||||||||||||||||||||||||||||||||||||
Date Documentation: | 15/8/2018 (Rev 1.0) |
...