Problem (Issue) Statement: | How to terminate output wiring connection to extra output points on XP-SNET controller and to configure the outputs | ||||||||||||||||||||||||||||||||||||||
Description: | A guide to terminate output wiring connection to extra output points on XP-SNET controller and to configure the outputs. | ||||||||||||||||||||||||||||||||||||||
Related Software: |
| ||||||||||||||||||||||||||||||||||||||
Related Hardware: | NIL | ||||||||||||||||||||||||||||||||||||||
System Application: |
| ||||||||||||||||||||||||||||||||||||||
Symptom and Finding: | NIL | ||||||||||||||||||||||||||||||||||||||
Cause: | For first time guide to terminate output wiring connection to extra output points on XP-SNET controller and to configure the outputs. | ||||||||||||||||||||||||||||||||||||||
Solution: | Summary:
|
Anchor | ||||
---|---|---|---|---|
|
Step 1: Refer to wiring diagram as shown below for wet contract output with NC (Normally Closed) contact type.
Figure 1: Wiring Diagram for Wet Contact Output with Normally Closed Contact Type
Step 2: Refer to wiring diagram as shown below for wet contact output with NO (Normally Opened) contact type.
Figure 2: Wiring Diagram for Wet Contact Output with Normally Opened Contact Type
Step 3: Refer to wiring diagram as shown below for dry contact output with NC (Normally Closed) contact type.
Figure 3: Wiring Diagram for Dry Contact Output with Normally Closed Contact Type
Step 4: Refer to wiring diagram as shown below for dry contact output with NO (Normally Opened) contact type.
Figure 4: Wiring Diagram for Dry Contact Output with Normally Opened Contact Type
To configure Alarm Controller Setup in xPortalNet Server:Anchor configurealarm configurealarm
Warning | ||
---|---|---|
| ||
|
.
.
Step 1: Go to Server Admin > System Device Setup > Alarm Controller > Add. The Add Alarm Controller window will be shown as below:
Figure 5: Add Alarm Controller Window
Info | ||
---|---|---|
| ||
To use the internal I/O configuration on XP-SNET controller, the Unit No field MUST be configured to 10. |
Step 2: The following message window will be prompted to show Record is Added. Click OK to continue.
Figure 6: Record Added Window
To configure Output Point Setup in xPortalNet Server:Anchor configureoutput configureoutput
Step 1: Go to Server Admin > System Device Setup > Input Point. The Input Setup window will be shown as below.
Figure 7: Output Setup Window
Step 2: Click Add to add a new output setup. The Add Output window will be shown as below.
Figure 8: Add Output Window
Step 3: Fill in the respective fields and click OK to save changes.
Figure 9: Add Output Window Fields Zoomed View
Info | ||
---|---|---|
| ||
|
Step 4: The following message window will be prompted to show that Record is Added. Click OK to continue.
Figure 10: Record Added Window
Step 5: Users can now proceed to configure built-in input points on the controller and create an Instruction Control configuration to specify the relationship between the Input & Output points.
Info | ||
---|---|---|
| ||
|
Date Documentation:
15/8/2018 (Rev 1.0)
...