Problem (Issue) Statement: | How to terminate sensor wiring connection to extra inputs on XP-SNET controller and to configure the inputs for alarm monitoring purposes | ||||||||||||||||||||||||||||||||||||||||||||||
Description: | A guide to terminate sensor wiring connection to extra inputs on XP-SNET controller and to configure the inputs for alarm monitoring purposes. | ||||||||||||||||||||||||||||||||||||||||||||||
Related Software: |
| ||||||||||||||||||||||||||||||||||||||||||||||
Related Hardware: | NIL | ||||||||||||||||||||||||||||||||||||||||||||||
System Application: |
| ||||||||||||||||||||||||||||||||||||||||||||||
Symptom and Finding: | NIL | ||||||||||||||||||||||||||||||||||||||||||||||
Cause: | For first time guide to terminate sensor wiring connection to extra inputs on XP-SNET controller and to configure the inputs for alarm monitoring purposes. | ||||||||||||||||||||||||||||||||||||||||||||||
Solution: |
. . Summary:
|
Anchor | ||||
---|---|---|---|---|
|
Step 1: XP-SNET controller can be configured to operate in two modes which allows users to configure the additional inputs for alarm monitoring purposes: Door access with alarm mode or alarm mode only.
Step 2: Configure the DIP switches for SETTING to assign the operation mode of the XP-SNET controller.
Figure 1: DIP Switches for SETTING on XP-SNET Controller
.
.
To terminate wiring for inputs:Anchor terminate terminate
Step 1: Please refer to the figure as below for Normally Closed (NC) Sensor Input termination.
Figure 2: Wiring Termination for Normally Closed Sensor Type
Step 2: Please refer to the figure as below for Normally Open (NO) Sensor Input termination.
Figure 3: Wiring Termination for Normally Opened Sensor Type
Info | ||
---|---|---|
| ||
For Alarm Monitoring purposes, all inputs points are required to add the 3.3kΩ resistor. |
.
.
Figure 4: IN1 to IN16 on XP-SNET Controller
Info | ||
---|---|---|
| ||
|
.
.
To configure Alarm Controller Setup in xPortalNet Server:Anchor configurealarm configurealarm
Step 1: Go to Server Admin > System Device Setup > Alarm Controller > Add. The Add Alarm Controller window will be shown as below:
Figure 5: Add Alarm Controller Window
Info |
---|
To use the internal I/O configuration on XP-SNET controller, the Unit No field MUST be configured to 10. |
Step 2: The following message window will be prompted to show Record is Added. Click OK to continue.
Figure 6: Record Added Window
To configure Input Point Setup in xPortalNet Server:Anchor configureinput configureinput
Step 1: Go to Server Admin > System Device Setup > Input Point. The Input Setup window will be shown as below.
Figure 7: Input Setup Window
Step 2: Click Add to add a new input setup. The Add Input window will be shown as below. Fill in the respective fields and click OK to save changes.
Figure 8: Add Input Window
Step 3: The following message window will be prompted to show that Record is Added. Click OK to continue.
Figure 9: Record Added Window
Step 4: Users can now proceed to configure built-in output points on the controller and create an Instruction Control configuration to specify the relationship between the Input & Output points.
Info | ||
---|---|---|
| ||
|
Date Documentation:
15/8/2018 (Rev 1.0)
...