Problem (Issue) Statement:

How to perform the ColdStart operation for the XP-SR200K controllerMicroEngine standalone controllers

Description:

This article will guide users on how to perform the ColdStart operation for the XP-SR200K controllerMicroEngine standalone controllers.

ColdStart operation must be performed if users forgot the MasterPIN to enter the Programming Menu to reset the MasterPIN to default settings.

Related Software:NIL
Related Hardware:
  • XP-SR200K
System Application:NIL
Symptom and Finding:

NIL

Cause:For first time guide on how to perform the ColdStart operation for the XP-SR200K controllerMicroEngine standalone controllers.
Solution:


Warning

The ColdStart Operation will erase all the memory in the

XP-SR200K

controller and reset all the settings to default. Proceed only if you are sure you want to reset the controller to default settings!

.

.

Summary:

  • To perform ColdStart operation for

    the XP-SR200K controller

    MicroEngine standalone controllers.

.


Step-by-step Guide:
  • To perform ColdStart operation for

    the XP-SR200K controller

    MicroEngine standalone controllers:

Step 1: Switch off the power for the XP-SR200K controller.

.

Step 2: Upon switching on the reader, it will enter the power up mode. The Red LED will be blinking at this stage for 10 seconds.

.

Step 3: In the power up mode while the Red LED is blinking, press and hold the exit button for 2 seconds. The controller will then reset to factory default settings. All the card users will also be cleared from the controller memory.

.

Info
titleNote

The default MasterPIN for the XP-SR200K MicroEngine standalone controllers is "123456". Users are advised to change the MasterPIN after performing the ColdStart operation.


Common Issues:

NIL

Porting Date:16/01/2020

...