How to Configure Jumper Settings for XP-SNET-E32R Output Relays when Connecting with XP-QNET Controller

Problem (Issue) Statement:

How to configure jumper settings for XP-SNET-E32R output relays when connect with XP-QNET controller

Description:

A guide to configure jumper settings for XP-SNET-E32R output relays when connecting with XP-QNET controller

Related Software:

  • xPortalNet HS PS v2.0.1.4

Related Hardware:

  • XP-QNET v2.04
  • XP-MK820 v2.03

System Application:

  • Alarm Monitoring System
  • Lift Masking Access System

Symptom and Finding:

NIL

Cause:

For first time guide to configure jumper settings for XP-SNET-E32R output relays when connecting with XP-QNET controller.

Solution:

Summary:

  • To configure jumper settings on XP-SNET-E32R output relays for Relay 1 to 16.

  • To configure jumper setting on XP-SNET-E32R output relays for Relay 17 to 32.

.

Step by Step:

  • To configure jumper settings on XP-SNET-E32R output relays for Relay 1 to 16:

Step 1: 
Location of the Jumper Setting DIP Switches for Relays 1 to 16 on XP-SNET-E32R 
Figure 1: Location of the Jumper Setting DIP Switches for Relays 1 to 16 on XP-SNET-E32R

.

Step 2: Refer to the table below to configure the jumper settings for relays 1 to 16 according to the specification for the output relays.
Jumper Settings for the Output Relay Configuration
Figure 2: Jumper Settings for the Output Relay Configuration

.

.

  • To configure jumper setting on XP-SNET-E32R output relays for Relay 17 to 32:

Step 1: The location of the jumper setting DIP switches for output relays number 17 to 32 are shown as below:  
Location of the Jumper Setting DIP Switches for Relays 17 to 32 on XP-SNET-E32R
Figure 3: Location of the Jumper Setting DIP Switches for Relays 17 to 32 on XP-SNET-E32R

.

Step 2: Refer to the table below to configure the jumper settings for relays 17 to 32 according to the specification for the output relays. 
Jumper Settings for the Output Relay Configuration
Figure 4: Jumper Settings for the Output Relay Configuration

.

Note

  • XP-QNET controller is able to support up to a maximum of 128 relay output.
  • The default jumper setting on XP-SNET-E32R extension board is Wet Contact with NO type.
  • The black bar indicates the pins required to be shorted.

Common Issues:

NIL

Date Documentation:

7/8/2020 (Rev 1.0)

PROOF-READ

.