Problem (Issue) Statement: | How to setup alarm monitoring system application using XP-GLS5000 controller at xPortalNet HS Server | ||||||
Description: | A guide to configure alarm monitoring system application using XP-GLS5000 controller at xPortalNet HS Server. | ||||||
Related Software: |
| ||||||
Related Hardware: |
| ||||||
System Application: |
| ||||||
Symptom and Finding: | NA | ||||||
Cause: | For first time configuration for alarm monitoring system application using XP-GLS5000 controller at xPortalNet Server. | ||||||
Solution: |
. . Summary:
|
For internal I/O configuration on XP-GLS5000 controller, the Unit No field MUST be configured to "10" |
.
.
Step 3: The following message window will be shown Record Added and click OKbutton.
Figure 9: Record Added window
.
Repeat steps 1 to 3 under this section for all extension boards (XP-SNET-E32R and XP-SNET-E248S) connected to the XP-GLS5000 controller board for alarm monitoring purposes. For applications where more than one extension board is connected to the XP-GLS5000 controller board, configure the address of the alarm panel in increasing order. For example, In the Add Alarm Controller window, configure the Unit No. field according to the extension board address configured. |
.
.
Step 1: Go to xPortalNet HS Server > Server Admin > System Device Setup > Output Point. The Output Setup window will be shown as below:
Figure 10: Output Setup Window
Step 2: Click Add to add a new output device. The Add Output Window will be shown as below. Fill up the respective field and click OK to save changes.
Figure 11: Add Output Window
The output point number starts from '0' for both extension boards XP-SNET-E32R and XP-SNET-E248. |
.
.
Step 3: The following message window will be prompted to show that Record is Added. Click OK to continue.
.
.
Step 1:Go to xPortalNet HS Server > Server Admin > System Device Setup > Input Point. The Input Setup window will be shown as below:
Figure 13: Input Setup Window
Step 2: Click Add to add a new input device. The Add Input window will be shown as below. Fill up the respective field and click OK to save changes.
Figure 14: Add Input Window
The input point number starts from '0' for the XP-SNET-E248 extension board. |
.
.
Step 3: The following message window will be shown Record Added. Click OKto continue.
Figure 15: Record Added Window
Step 4: Users can then proceed to create an Instruction Control to configure the relationship between the Inputs and Outputs.
Users can refer to How to Configure Instruction Control for Alarm Monitoring System Application at xPortalNet HS Client for the complete steps. |
Common Issue
NA
Date Documentation:
29/5/2019
.
|
.
.