Problem (Issue) Statement: | How to connect XP-GLS300 controller to XP-SNET-E32R extension board for Lift Masking Application | |||
Description: | A guide to connect XP-GLS300 controller to XP-SNET-E32R extension board for Lift Masking System Application. | |||
Related Software: | NIL | |||
Related Hardware: |
| |||
System Application: |
| |||
Symptom and Finding: | NIL | |||
Cause: | For first time hardware wiring connection between XP-GLS300 controller to XP-SNET-E32R Extension Board for Lift Masking System Application | |||
Solution: | Summary
|
Please note that the SETTING DIP Switches are inverted; and that the ON positions for the DIP switches are at the bottom positions, as denoted by the inverted "ON" label on the DIP switch body. |
Step 2: After configuring the DIP switches, press "RESET" on the XP-GLS300 controller board to reset the controller in order for the new setting to take effect.
Step 1: Wiring diagram: XP-GLS300 controller to XP-SNET-E32R extension board
Figure 2: Wiring Diagram of XP-GLS300 Controller and XP-SNET-E32R Extension Board
Users can refer to How to Configure Address Unit No on XP-SNET-E32R Extension Board for the complete steps to configure address settings on XP-SNET-E32R |
XP-GLS300v4 controller can only be connected to Plato Reader model RM80C/KLS and RM80MS |
Date Documentation:
6/7/2018 (Rev 1.0)
.
|
.
.