Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

Version 1 Next »

Problem (Issue) Statement:

How to connect Fire Alarm signal to XP-SNETv2 or XP-SNETv4 controller

Description:

A guide to connect fire alarm signal to XP-SNETv2 / XP-SNETv4 controller.

Related Software:

  • xPortalNet v1.5.0.110

Related Hardware:

  • XP-SNET v3.65
  • Plato Reader C80s v5.03

System Application:

  • Lift Masking Access System

Symptom and Finding:

NIL

Cause:

For first time connection for fire alarm signal to XP-SNETv2 / XP-SNETv4 controller.

Solution:

Summary:

  • To connect fire alarm signal to XP-SNETv2 / XP-SNETv4 controller.


Step-by-Step Guide:

  • To connect fire alarm signal to XP-SNETv2 / XP-SNETv4 controller:

Step 1: Please refer to the wiring diagram: XP-SNETv2 / XP-SNETv4 controller to Fire Alarm signal connection.

Figure 1: Fire Alarm Signal Connection to XP-SNETv2 / XP-SNETv4 Controller

Note

  • For normal operations, fire alarm termination requires Normally Closed (NC) dry contact on XP-SNETv2 and XP-SNETv4 controllers to deactivate fire alarm mode.
  • To trigger the fire alarm, the fire alarm panel needs to send a Normally Opened (NO) dry contact to XP-SNETv2 / XP-SNETv4 controllers via the Fire Alarm terminals.

Date Documentation:

31/7/2018 (Rev 1.0)

PROOF-READ

  • No labels