Warning |
---|
|
XP-SNET-GAC currently do not support odd numbered card lengths, e.g. 5, 7, 9 card number lengths. |
Summary:
Info |
---|
|
Global Antipassback feature is only supported for LAN Network Communications. |
Step-by-step Guide:
Step 1: Go to xPortalNet Client > Data Setup > System Setting > Controller.
Step 2: In the Controller Setup window, select the controller to be assigned as client GAC controller to enable AntiPassback feature and click Modify.
Figure 1: Edit Controller Window
Step 3: At the AntiPassback Function Enabled field, click on the drop-down dialog box and select Yes.
Figure 2: AntiPassback Function Enabled Setting
Step 4: Under the Client Global AntiPassback Settings section, configure the respective fields according to the table that follows. Click OK to save the changes.
Figure 3: Client Global AntiPassback Settings Section in Edit Controller Window
Step 6: The software will prompt the following message window to prepare the process of sending GAC Parameters Command to client GAC controller. Wait for the process to finish and click OK on Delivery Report to continue.
Figure 4: Preparing GAC Parameters Command Window
Step 7: To configure another Client GAC controller, repeat steps 1 to 5.
Step 1: Go to xPortalNet Client > Data Setup > System Setting > Door.
Step 2: The Door Setup window will be shown. Select the specific door to configure zone code click Modify to continue.
Step 3: The Edit Door window will then be shown. Configure the AntiPassback Entry & Exit Zone Code accordingly and click OK to save the changes.
Figure 5: AntiPassback Entry and Exit Zone Code in Edit Door Window
Step 4: The software will then prompt the following message window to indicate that the Record is Updated. Click OK to continue.
Figure 6: Record Updated Window
Step 5: The Send Data and Command window will then be shown. Wait for the send controller setting process to complete before clicking Close to continue.
Figure 7: Send Data and Command Window
Step 6: To configure zone code for another Client GAC controller, repeat steps 1 to 5.
Anchor |
---|
| sendconfigurationsetting-110 |
---|
| sendconfigurationsetting-110 |
---|
|
To send the configuration settings to Door Controller:
Step 1: Go to xPortalNet Client > Device Comm > Send Door Setting
Figure 8: Send Door Setting Button in Device Comm Icon
Step 2: Select both the SNET-GAC controller and the client GAC Controller. Click Send All Setting.
Figure 9: Send Door Controller Settings Window
To observe transaction logs after completing configuration settings to ensure that Global AntiPassback is enforced:
Step 1: Flash a test card on entry reader more than twice. Ensure that the Latest Event List recorded a Valid Entry Access transaction, followed by AntiPB Violation transaction logs.
Figure 10: Valid Entry Access and AntiPB Violation Transaction Logs