Step 1: Run xPortal3000 Server Configuration Manager. Ensure that the Service State is "Running". Click Start if the Service State is "Stopped".
Figure 1: xPortal3000 Server Configuration Manager Window
Step 2: Open xPortal3000 client. Click Control Panel.
Figure 2: Control Panel Icon
Step 3: The Control Panel menu will be shown. Click System Properties.
Figure 3: Control Panel Menu
Step 4: The System Properties window will be shown. Click Modify. Go to General Tab and select "Yes" at the Fire Alarm Auto Release field to enable this feature. Click OK to save the changes.
Figure 4: System Properties Window
Step 5: The following message window will be shown to indicate that the Record is Updated. Click OK to continue.
Figure 5: Record Updated Window
Step 3: The Delivery Report window will be shown. Ensure that all the controller settings are sent successfully. Click OK to complete the process.
Figure 6: Delivery Report Window
.
.
Step 1: Go to xPortalNet Client > Device Comm > Send Door Setting.
Step 2: The Send Door Controller Settings window will be shown. Check the desired controller's checkbox and click Send All Settings.
Figure 7: Send Door Controller Settings Window.
.
.
Step 1: Go to Device List > Controller List. Ensure that all door controller statuses are Normal.
Figure 8: Controller List under Device List
Step 2: Go to Device List > Door List. Ensure that all related Door statuses are Up and that Security status is Y.
Figure 9: Door List under Device List
.
.
Step 1: At the Latest Event List window, ensure that the transaction Release All Doors On Fire Alarm, Door Security Off from all related doors and Fire Alarm On are recorded from the source controller.
Figure 10: Latest Event List Window
Step 2: At the Latest Alarm Event List, ensure that the Fire Alarm On transaction is logged.
Figure 11: Latest Alarm Event List recording the Fire Alarm On Transaction
Step 5: Also, ensure that all electromagnetic lock for all physical doors are released.
Info |
---|
|
The electromagnetic lock for the physical doors will be released when the controller and door statuses are Up. |
Step 1: Go to Device Comm > Send Door Command.
Figure 12: Send Door Command Icon
Step 2: The Send Door Command window will be shown. Select the desired door name and click Security On.
Figure 13: Send Door Command Window
Step 3: The Delivery Report window will be shown. Ensure that all the door commands are successfully sent. Click Close to complete process.
Figure 14: Delivery Report Window
Step 4: All physical doors selected will return to normal, secure operation.
Info |
---|
|
Users have to ensure that the necessary fire safety measures are taken and confirmed that the building is safe before returning the doors to normal secure operation. |