Problem (Issue) Statement:

How to configure RS485 address for XP-M1000i / XP-M1300i controller?

Description:

A guide to configure RS485 address for XP-M1000i / XP-M1300i controller.

Related Software:

NA

Related Hardware:

  • XP-M1000i
  • XP-M1300i

System Application:

Single Door Access

Symptom and Finding:

NA

Cause:

For first time configuration on RS485 address for XP-M1000i / XP-M1300i controller.

Solution:

Note

For RS485 wiring connections between the controllers and the Server PC, the Daisy Chain connection topology is the recommended wiring connection.

Warning!

RS485 wiring connection using the Star topology may result in controller communication issues!

Summary

  • To perform ColdStart after first time power up of the XP-M1000i / XP-M1300i controller.

  • To configure the RS485 address of the controller by changing the DIP switch on the controller board.

Step-by-step Guide:

  • To perform ColdStart after first time power up of the XP-M1000i / XP-M1300i controller:

Step 1: Press and hold the ColdStart button on the controller board.

Step 2: Turn OFF the power supply.

Step 3: Turn ON the power supply.

Step 4: Release the ColdStart button after 3 seconds. The controller will respond with a long beep to indicate that the ColdStart process is in effect.

Note

Users are advised to perform ColdStart operation once for every fresh installation unless advised otherwise.


  • To configure the RS485 address of the controller by changing the DIP switch on the controller board:

Step 1: Configure the RS485 address (Unit No.) according to the following diagram:
 
Figure 1: DIP Switch Configuration for XP-M1000i / XP-M1300i Controller

Date Documentation:

19/6/2018 (Rev 1.1)