Problem (Issue) Statement: | How to troubleshoot RS485 Communication between controller and xPortal software |
Description: | Controller failed to establish RS485 communication with the xPortal software. |
Related Software: | |
Related Hardware: | - XP-GT1200L
- XP-GT3200L
- XP-GT1200LABX
- XP-GT3200LABX
- XP-GT3200LE
- XP-GT3200LCPX
- XP-GT500LE
- XP-GTR1200L
- XP-GTR3200L
|
System Application: | NIL |
Symptom and Finding: | - Controller's status in the Device List is shown as "Down"
- The software's Latest Event List failed to record any transaction updates from the controller
- Controller setting is not updated when users download settings from the software
- In the software Delivery Report, the delivery status is shown as "Sent Error" when downloading settings or updating the card user info to the controller
|
Cause: | - Wiring termination issues between controller and MCI or USB-to-serial converter
- Incorrect Comm Port No selected
- Incorrect controller Unit No. / System Addr No. selected in the controller and software xPortal Server
- Incorrect Baud Rate Setting between the controller, MCI, and/or xPortal Server
- MCI unit may be faulty
- Comm Port may be faulty
|
Solution: | Summary:. Step-by-step Guide: To check and reconfirm the wiring termination between the controller and MCI or USB-to-serial converter:
Step 1: Check and reconfirm that the wiring termination between the controller and MCI or USB-to-serial converter are terminated correctly and properly:
Figure 1: Wiring Termination from the XP-GT or XP-GTR (old series) to the MCI unit . Figure 2: Connection of Multiple XP-GT (old series) Controllers to One MCI Unit to be Connected to PC
. . . To check and reconfirm software and hardware configuration settings:
Step 1: In the Edit Connection window, check and ensure that the Comm No and the Speed is configured according to the appropriate hardware connections
Figure 3: Add Connection Window . . . Step 2: In the Edit Controller window, check and ensure that the controller's Unit No is configured according to the System Address in General Parameter of the controller's programming menu.
Figure 4: Unit No Field in Edit Controller Window . Figure 5: System Address Setting in General Parameter Menu on XP-GT / XP-GTR (old series) Controller
. Step 3: Check and ensure that the software is allowed communication access through the Windows Firewall and the respective antivirus software. . . To send in the MCI unit for repairs:
Step 1: If none of the above works to solve the issue, users are advised to swap the MCI with a known to be functioning unit of MCI to identify if the MCI unit is faulty. . Step 2: If the MCI unit is tested to be faulty, users are advised to send the faulty MCI unit for repairs with the MicroEngine Service Center. |
Common Issues: | NIL |
Porting Date: | 22/2/2019 |