Problem (Issue) Statement: | How to connect fire alarm signal to XP-M1000X controller and to configure fire alarm lock release feature | ||||||||||
Description: | This article will guide users to connect fire alarm signal to XP-M1000X controller and to configure fire alarm lock release feature. | ||||||||||
Related Software: | NIL | ||||||||||
Related Hardware: |
| ||||||||||
System Application: | NIL | ||||||||||
Symptom and Finding: | NIL | ||||||||||
Cause: | For first time guide on how to connect fire alarm signal to XP-M1000X controller and to configure fire alarm lock release feature. | ||||||||||
Summary:
. . Step-by-step Guide:
Step 1: Please refer to the wiring diagram: XP-M1000X controller to fire alarm connection via the MAS-RBU relay board. .
. .
Step 1: After ensuring that the fire alarm signal is properly connected to the MAS-RBU relay board, users have to proceed to configure the fire alarm lock release in XP-M1000X controller. Enter the Programming Menu at the controller.
. . Step 2: Press 1 for Sys Menu > 2 for Door Para. The screen below will be shown. . Step 3: Press "#" to proceed to the next item in the Door Para menu until users reached the FireRls [OFF] screen is shown. Edit the values for the item displayed to [ON] by pressing "0" to toggle between the settings. . Step 4: Press "#" to proceed to the next item in the Door Para menu until the Save Changes page is shown. Press the "#" to save the changes and exit from the Door Para menu. | |||||||||||
Common Issues: | NIL | ||||||||||
Porting Date: | 30/10/2019 |
...