Problem (Issue) Statement: | When user flashed card on exit Plato reader, the reader responds with only one beep sound. | |||||
Description: | After installing the XP-M1000i door controller and completing the cable termination to entry & exit Plato readers, upon power up, when user flashed card on exit Plato reader, the reader responded with only one beep sound. | |||||
Related Software: | NIL | |||||
Related Hardware: |
| |||||
System Application: |
| |||||
Symptom and Finding: | After hardware installation and configuration completes, user flashed card on both readers. Entry reader responded with 4 beep sounds but exit reader responded with only one beep sound. | |||||
Cause: | The DIP-switches for ADDRESS on exit Plato reader was not assigned. | |||||
Solution: | Summary
Step by step guide:
Step 1: Switch off the XP-M1000i controller's power source or disconnect the reader from the XP-M1000i controller.
| |||||
Date Documentation: | 23/7/2018 (Rev 1.0) |