Problem (Issue) Statement:

How to configure Instruction Control for alarm monitoring system application at xPortalNet Client

?

Document No:

ID-000059

Categories:

Knowledge Base

Type:

Software configuration

Technical Level:

1

Related Project Name:

  • Harrington, Kota Kinabalu Sabah (SI: MIE)
  • DBS, Taman Desa (SI: YL System)
  • Uptown Mall (SI: SKA Technologies S/B)
  • Women And Child Hospital (SI: EV Dynamic S/B)

    Site Deployment Date:

    8/3/2017

    Description:

    A guide to configure Instruction Control for alarm monitoring system application at xPortalNet Client.

    Related Software:

    • xPortalNet v1.5.0.122

    Related Hardware:

    • XP-SNETv2 v3.48
    • XP-SNET-E32R
    • XP-SNET-E248

    System Application:

    Alarm Monitoring System

    Symptom and Finding:

    NA

    Cause:

    For first time configuration on Instruction Control for alarm monitoring system application at xPortalNet Client

    Solution:


    Warning
    titleWarning!
    • Users are not recommended to run any xPortal software in Windows XP operating system as the system is unstable

    • Users are also advised to stop the xPortal Services before shutting down the Server PC to prevent any missing transaction issues.

    .

    .

    Warning
    titleWarning!

    The XP-SNET controller will not send fire alarm signal over to the connected XP-SNET-E32R and/or XP-SNET-E248 extension boards if the configuration settings for the XP-SNET controller is not completed.

    Complete the configuration settings for XP-SNET controller in order for XP-SNET-E32R and/or XP-SNET-E248 to respond accordingly to fire alarm signals.

    .

    .

    Summary


    Step by Step:

    • Anchor
      service-running-59
      service-running-59
      Ensure that the xPortalNet Services is Running:

    Step 1: Open xPortalNet Comm Service.


    Step 2: Ensure that the xPortalNet Comm Service Status is Running.
    xPortalNet Comm Service Running Pop-up MessageImage Modified
    Figure 2: xPortalNet Comm Service Running pop-up message


    • Anchor
      alarm-monitoring-configured-59
      alarm-monitoring-configured-59
      Ensure that the alarm monitoring controller settings are configured in xPortalNet Server:

    Info
    titleKnowledge Base Link

    Users can refer to 

    ID-000058
    ? for

     for the complete procedures.



    • Anchor
      configure-instruction-control-59
      configure-instruction-control-59
      To configure Instruction Control setup at xPortalNet client:

    Step 1: Go to xPortalNet Client > System Setting > Instruction Control. The Instruction Setup window will be shown as below:
    Instruction Setup WindowImage Modified
    Figure 1: Instruction Setup Window


    Step 2: Click Add to create a new instruction. The Add Instruction window will be shown as below. Fill in the respective fields and click OK to save changes.
    Add Instruction WindowImage Modified
    Figure 2: Add Instruction Window

    Image Removed


    Image Added


    Info
    titleNote
    • represents required field
    • Users can add up to a maximum of 8 Inputs and Outputs in one Instruction Setup.




    Step 3: Repeat steps 1 and 2 to add additional Instruction Setups as necessary.

    Step 4: The following message window will be prompted to show that Record is Added. Click OK to continue.
    Record Added WindowImage Modified
    Figure 3: Record Added Window


    • Anchor
      send-door-setting-59
      send-door-setting-59
      To send Door Settings to Controller after completing
      the configuration:

    Step 1: After completing the configuration settings, users MUST send all settings to the controller.


    Step 2: Go to Device Comm > Send Door Setting.
    Send Door Setting ButtonImage Modified
    Figure 4: Send Door Setting Button


    Step 3: Select the controller to send all settings. Click Send All Settings to send all configuration settings to the selected controller.


    Step 4: The Delivery Report will be prompted. Ensure that software have sent all configuration settings successfully.


    • Anchor
      observe-59
      observe-59
      To observe the device status:

    Step 1: To check the status of the controller, go to xPortalNet Client > Device List > Controller List to verify that the controller Status is Up.
    Controller List under Device List TabImage Modified
    Figure 5: Controller List under Device List tab


    Step 2:To check the status of the alarm controller, go to xPortalNet Client > Device List > Alarm Controller List to verify that the alarm controller Status is Up.
    Alarm Controller List Under Device List TabImage Modified
    Figure 6: Alarm Controller List under Device List tab


    Step 3: To check the status of the output, go to xPortalNet Client > Output List to observe the output status.
    Output List Under Device List TabImage Modified
    Figure 7: Output List under Device List tab

    Image Removed


    Image Added


    Step 4: To check the status of the input, go to xPortalNet Client > Input List to observe the input status.
    Input List Under Device List TabImage Modified
    Figure 8: Input List under Device List tab

    Image Removed


    Image Added

    Date Documentation:

    24/5/2018 (Rev 1.0)

    Status
    subtletrue
    colourYellow
    titleProof-read

    .

    Section
    bordertrue


    Column
    width100%

    Related Articles.

    Containing the label "alarm-monitoring-mode"

    Filter by label (Content by label)
    showLabelsfalse
    max6
    showSpacefalse
    sorttitle
    cqllabel = "alarm-monitoring-mode" and space = "MKB"


    .

    ...

    .

    Choices for confluence
    _id5d09d34324c64e0020444e9a