Problem (Issue) Statement:

How to configure fire alarm door release and fire alarm group at xPortalNet

Description:

A guide to configure fire alarm door release and fire alarm group at xPortalNet.

Related Software:

  • xPortalNet v1.5.0.123
  • SQL Server Express 20008 R2 (Version: 10.50.4000.0)

Related Hardware:

  • XP-M1000iv2
  • XP-M2000i
  • XP-GT3500L / ABL*
  • XP-GTR1500L / ABL*


Info
titleNote

*For XP-GT3500L / ABL and XP-GTR1500L / ABL controllers, users have to be sure to terminate the fire alarm signal into the controller's fire alarm terminal block instead of the MAS-RBM / MAS-RBU's fire alarm terminal block in order to use the functions highlighted by this article.


System Application:

  • Software configuration for fire alarm release.

Symptom and Finding:

NA

Cause:

For first time configuration on fire alarm door release and fire alarm group at xPortalNet.

Solution:


Warning
titleWarning!
  • Users are not recommended to run any xPortal software in Windows XP operating system as the system is unstable

  • Users are also advised to stop the xPortal Services before shutting down the Server PC to prevent any missing transaction issues.

.

.

Summary


Step-by-step Guide:

  • Anchor
    enable-67
    enable-67
    To enable Fire Alarm Door Release setting:

Step 1: Go to xPortalNet Server > Server Admin > System Properties.


Step 2: The following message window will be shown. Click OK to continue.
xPortalNet Comm Server Message Window
Figure 1: xPortalNet Comm Server Message Window

Info
titleNote

This message window is prompted because users have yet to upload the company logo to the System Properties.



Step 3: The System Properties window will be shown as below. Click Modify.
System Properties Window
Figure 2: System Properties Window


Step 4: The Edit System Properties window will be shown. Configure the Fire Alarm Door Release to "Y" and click OK to save the changes.
Edit System Properties Window
Figure 3: Edit System Properties Window

Info
titleNote

Fire Alarm Door Release configuration is only applicable to XP-SNET v4, XP-M2000i and XP-M1000i controller models only. 



Step 5: The following message window will be shown to indicate that the Record is Updated. Click OK to continue.
Record Updated Window
Figure 4: Record Updated Window


Step 6: The following message window will then be prompted as a reminder to users to send the door settings to the controller. Click OK to continue.
Send Door Setting Reminder Window
Figure 5: Send Door Settings Reminder Window


  • Anchor
    configure-67
    configure-67
    To configure Fire Alarm Group:

Step 1: Go to xPortalNet Client > Data Setup > System Setting > Fire Alarm Group > Add.


Step 2: The Add Fire Alarm Group window will be shown as below. Fill in the respective fields and click OK to save changes.
Add Fire Alarm Group Window
Figure 6: Add Fire Alarm Group Window





Step 3: The following message window will be shown to indicate that the Fire Alarm Group has been added successfully. Click OK to continue. Back at the Fire Alarm Group Setup window, click Close.
Fire Alarm Group is Added Successfully Window
Figure 7: Fire Alarm Group is Added Successfully Window


  • Anchor
    download-67
    download-67
    To download Door Settings:

Step 1: Go to xPortalNet Client > Device Comm > Send Door Setting.


Step 2: The Send Door Controller Settings window will be shown. Check the desired controller's checkbox and click Send All Settings.
Send Door Controller Settings Window
Figure 8: Send Door Controller Settings Window


Step 3: The Delivery Report window will be shown. Please wait for the Send Data and Command process to complete before clicking Close.
Delivery Report Window
Figure 9: Delivery Report Window


  • Anchor
    observe-before-67
    observe-before-67
    To observe event transaction before
    Fire Alarm is triggered:

Step 1: Go to xPortalNet Client > Device List > Controller List. Ensure that all related door controllers from the Fire Alarm Group have the controller status as UP and that the Fire Alarm Status is Normal.
Controller List under Device List Tab
Figure 10: Controller List under Device List

Step 2: Go to Device List > Door List. Ensure that all related door statuses are UP, Security On and Door Closed State.
Door List under Device List tab
Figure 11: Door List under Device List

Step 3: At the Latest Event List window, ensure that the transaction Fire Alarm Off is logged from the master controller under normal condition (Fire Alarm not triggered).
Latest Event List Window
Figure 12: Latest Event List Window


  • Anchor
    observe-after-67
    observe-after-67
    To observe event transaction after Fire Alarm is triggered:

Step 1: At Latest Event List window, ensure that the transaction Release Doors Upon Fire Alarm, Door Security Off from all related doors and Fire Alarm On is logged from the master controller.
Latest Event List Window Logging Fire Alarm Statuses
Figure 13: Latest Event List Window Logging Fire Alarm Statuses

Step 2: Go to Device List > Controller List. The master controller's Fire Alarm status will be shown as Triggered.
Master Controller's Fire Alarm Status Shown as Triggered
Figure 14: Master Controller's Fire Alarm Status Shown as Triggered

Step 3: Go to Device List > Door List. The Current Security status will be shown as Off.
Door's Current Security Status Shown as Off
Figure 15: Door's Current Security Status Shown as Off

Step 4: At the Latest Alarm Event List, ensure that the Fire Alarm On transaction is logged.
Latest Alarm Event List Logging the Fire Alarm On Transaction
Figure 16: Latest Alarm Event List Logging the Fire Alarm On Transaction

Step 5: Also, ensure that all electromagnetic lock for all physical doors selected in the Fire Alarm Group are released and the electromagnetic lock for the door controlled by the Master Controller is also released. 


Info
titleNote

The electromagnetic lock for the physical doors will be released when the controller and door statuses are Up.




  • Anchor
    configure-normal-67
    configure-normal-67
    To configure the Doors back to normal operation:

Step 1: Go to xPortalNet Client > Device Comm > Send Door Command.

 
Step 2: The Send Door Command window will beshown. Select the door names that are in the Fire Alarm Group List and click Security On.
Send Door Command Window
Figure 17: Send Door Command Window


Step 3: The Delivery Report window will be shown. Wait for the door command sending process to complete and click Close to continue.
Delivery Report Window
Figure 18: Delivery Report Window


Step 4: All physical doors selected in Fire Alarm Group will return to normal, secure operation.

Info
titleNote

Users have to ensure that the necessary fire safety measures are taken and confirmed that the building is safe before returning the doors to normal secure operation.


Date Documentation:

31/5/2018 (Rev 1.0)

...