Problem (Issue) Statement: | How to set Output Time Zone for XP-SNET controller in xPortalNet software | |||||||
Description: | This article will guide users to set Output Time Zone for XP-SNET controller in xPortalNet software. | |||||||
Related Software: |
| |||||||
Related Hardware: | NIL | |||||||
System Application: | NIL | |||||||
Symptom and Finding: | NIL | |||||||
Cause: | For first time guide to set Output Time Zone for XP-SNET controller in xPortalNet software. | |||||||
Solution: | Summary:
. . Step-by-step Guide:
Step 1: At the XP-SNET controller, set the DIP switch 2 and 3 of the SETTING DIP switch to the ON position. . Step 2: Reset the controller after the DIP switches are adjusted. . Step 3: Go to xPortalNet Server > Server Admin > System Device Setup > Alarm Controller > Add. The Add Alarm Controller window will be shown. Set the Unit No. as "10", and select the Model No as "Built-In IO". . Step 4: Next, go to xPortalNet Server > Server Admin > System Device Setup > Output Point > Add. The Add Output window will then be shown. .
. . Step 5: Go to xPortalNet Client > Data Setup > System Setting > Output > select the correct Output > Modify. The Edit Output window will then be shown. Under the Output TZ field, select the pre-configured Time Zone. .
| |||||||
Common Issues: | NIL | |||||||
Porting Date: | 22/01/2020 |
...