Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Problem (Issue) Statement:

How to configure RS485 address for XP-M1000i / XP-M1300i controller

Description:

A guide to configure RS485 address for XP-M1000i / XP-M1300i controller.

Related Software:

NA

Related Hardware:

  • XP-M1000i
  • XP-M1300i

System Application:

Single Door Access

Symptom and Finding:

NA

Cause:

For first time configuration on RS485 address for XP-M1000i / XP-M1300i controller.

Solution:



Info
titleNote

For RS485 wiring connections between the controllers and the Server PC, the Daisy Chain connection topology is the recommended wiring connection.

.

.

Warning
titleWarning!

RS485 wiring connection using the Star topology may result in controller communication issues!

.

.

Summary

  • To perform ColdStart after first time power up of the XP-M1000i / XP-M1300i controller.

  • To configure the RS485 address of the controller by changing the DIP switch on the controller board.

.

Step-by-step Guide:

  • To perform ColdStart after first time power up of the XP-M1000i / XP-M1300i controller:

Step 1: Press and hold the ColdStart button on the controller board.

.
Step 2: Turn OFF the power supply.

.
Step 3: Turn ON the power supply.

.
Step 4: Release the ColdStart button after 3 seconds. The controller will respond with a long beep to indicate that the ColdStart process is in effect.

.

Info
titleNote

Users are advised to perform ColdStart operation once for every fresh installation unless advised otherwise.

.

.

  • To configure the RS485 address of the controller by changing the DIP switch on the controller board:

Step 1: Configure the RS485 address (Unit No.) according to the following diagram:
 
Figure 1: DIP Switch Configuration for XP-M1000i / XP-M1300i Controller

Date Documentation:

19/6/2018 (Rev 1.1)

...